TERMS:

Cut-out - Temperature sensed by the

controller that shuts the compressor

off.

Cut-in - Temperature sensed by the

controller that turns the compressor

on.

REQUIRED TOOLS

Phillips Head Screwdriver

5/64" or 2 mm Allen Wrench

T-7 Torx Wrench

STEP 1

Unplug the cooler.

STEP 2

Remove the screws that secure the

temperature control to the inset box.

STEP 3

Pull out gently from cabinet.

STEP 4

For high elevation installations, it

may be necessary to "warm-up" the

set points. To make the adjustment,

insert the appropriate tool in each

adjustment screw and turn 1/4 of a

revolution clockwise (to the right).

This procedure will adjust both

the cut-in and cut-out about 2°F

warmer.

STEP 5

Make sure to reconnect the pink

wire to the proper spade terminal

when reinstalling.

NOTE:

Mechanical temperature

controllers are affected when

functioning at high altitude. The

cut-in and cut-out

temperatures will be colder than

when the controller functions

closer to sea level

Danfoss Temperature Control (High Altitude Adjustment Only!)

Cut-out Adjustment Screw Allen (5/64"
or 2 mm) (clockwise for warmer)

Cut-in Adjustment Screw Torx (T-7)
(clockwise for warmer)

Compressor Connection (pink)

Compressor Connection (pink)

TEMPERATURE CONTROL ADJUSTMENT FOR

HIGH ALTITUDE ONLY!

INSTALLATION / OPERATION INSTRUCTIONS