G7 ASD Multi-Protocol Communication Option and PG Feedback Option Manual

17

8.2 Modbus RTU Configuration

When parameter F890 is selected for Modbus RTU communications, then the additional Network
Configuration Parameters are assigned the functions as indicated in Table 6.

Table 6: Modbus RTU Network Configuration Parameters

Parameter Function

Settings

Default

Value

F891 Baud

Rate

0: 300 baud
1: 600 baud
2: 1200 baud
3: 2400 baud
4: 4800 baud
5: 9600 baud
6: 19.2 kbaud
7: 38.4 kbaud

5

F892

Parity & Stop Bits

0: no parity (1 stop bit)
1: no parity (2 stop bits)
2: even parity
3: odd parity

1

F893

Response Delay

0 ~ 200 (0.00s ~ 2.00s)

0

F894

Unused

N/A (Always 0)

0