11.5.3 DeviceNet Object

Class Code 0x03. The DeviceNet Object provides for the configuration and status of a DeviceNet port.

11.5.3.1 DeviceNet Object Class Attributes

Attribute

ID

Access

Rules

Name

Data

Type

Description

Default

Value

1

Get

Revision

UINT Revision of this object.

2

11.5.3.2 DeviceNet Object Instance Attributes

Attribute

ID

Access

Rules

Name Data

Type

Description

Default

Value

1

Get

MAC ID

USINT

Node address

--

2

Get

Baud Rate

USINT

Baud rate

--

3

Get / Set

BOI

BOOL

Bus-off interrupt

0

4

Get / Set

Bus-Off
Counter

USINT

Number of times CAN
went to the bus-off state

0

5 Get

Allocation

Information

STRUCT

of:

Allocation

Choice Byte

BYTE

0

Master’s MAC

ID

USINT

MAC ID of master

0xFF

Notes

• The MAC ID and Baud Rate attributes are not settable via the network (they are set via the

drive’s parameter settings). Attempting a

Set service will result in a “Service Not Supported”

error.

• The setting of the BOI attribute is saved in the DeviceNet unit’s internal EEPROM. If the BOI

value is set to TRUE, the DeviceNet interface will attempt to restart the network interface on
the occurrence of a CAN bus-off event. This will continue to be the behavior until the Bus-Off
Counter attribute achieves a value of 255. If a CAN bus-off event occurs after this point, the
unit will not attempt to restart the network interface: it will remain faulted and isolated from the
network until the drive is reset or power cycled.