8 led indicators, 9 register summary – Toshiba G7 User Manual

Page 50

Advertising
background image

G7 ASD Multi-Protocol Communication Option and PG Feedback Option Manual

43

registers read / written, more time may actually be required by the Modbus interface before a complete
response is formulated and ready to be returned to the network.

The response delay timer value is read only upon initialization. Therefore, if the delay value is changed,
the drive must be reset for the new value to take effect.

10.2.8 LED Indicators

If the ASD’s “Inverter Number” parameter (F802) is not set to a value between 1 and 247, the Module
Status LED will flash red upon initialization to indicate the configuration error.

Whenever a faulty Modbus packet is detected, the Network Status LED will briefly flash red to indicate
the faulty packet. This can be used as a helpful indicator when communications are not working, and
will usually be the result of incompatible network settings (baud rate, parity, etc.) or reversed RS-485
wires.

10.2.9 Register Summary

Table 25 presents an overview of all accessible information within the entire Modbus register map.
Although the majority of the mapping directly accesses the corresponding ASD registers, not all ASD
registers are available. The specific ASD registers that can be accessed are defined in the Toshiba

ASD

Operation Manual and/or the ASD Serial Interface Manual. In addition, the accessible registers, their
access behaviors and data ranges may vary depending on such issues as the drive’s capacity and control
firmware revision.

Table 24 lists the Modbus registers that access local information on the Multicom interface. These
items are also indicated in Table 25.

Table 24: Local Modbus Interface Access

Modbus Register

Function

Read / Write

Adjustment Range

0x0C00~0x0C1F /

0xFC00~0xFC1F

PPR data registers

According to

referenced

register

According to referenced

register

0x0C20~0x0C3F /

0xFC20~0xFC3F

PPR address registers

Read/Write

0x0001 ~ 0xFFFF

(1

10

~ 65535

10

)

0x0C82 / 0xFC82

Multicom interface

firmware

version/revision

Read only

High byte = firmware version

Low byte = firmware revision

Advertising