Advanced functions – Xantrex Technology LINK 10 User Manual

Page 33

Advertising
background image

33

Advanced Functions

CAUTION: If you set the discharge floor high, such as 50%, and

continue to discharge well beyond this point, you will notice that the
bar graph does not "fill up" until you have charged the battery above
the discharge floor. In other words, if you set the discharge floor at

50% and discharge 75%, you must recharge back up to the 50% level
before your bar graph and time of operation will again give you
meaningful information.

DEFAULT: 100%

RANGE: 50–100%

Step: 5%

F10–F12 SEE LOW BATTERY ALARM, PAGES 35–38

F13 SEE HIGH VOLTAGE NOTES, PAGE 50

F14 ENABLE LOW BATTERY ALARM

In versions of the Link 10 equipped with the Low Alarm Switch, this
function allows the Low Battery Alarm to be disabled.

DEFAULT: OFF

RANGE: ON, OFF

F15 SOFTWARE REVISION

Displays revision of software.

Please note that the software enhancements to the Link 10 may not be

retrofitted into earlier versions of this product. If the Link 10 has serial
number 005000 or larger, it will come with software version E1.3 or
greater installed. Earlier versions of the Link 10 do not support

temperature sensing, small amp-hour increments, separate alarms for
meter power and low battery conditions. Early versions display 255
instead of CCC when the battery is being charged.

Advertising
This manual is related to the following products: