Alarm functions, Refer to f14 in the owner's manual – Xantrex Technology LINK 10 User Manual

Page 36

Advertising
background image

36

Alarm Functions

F10 LOW BATTERY ALARM OFF (RECHARGE) SET POINT

Once the Low Battery Alarm is activated, recharging the battery to

this point turns the alarm OFF. This recharged point must always be at
least 10% higher than Low Battery Line closure point.
DEFAULT: 70% RANGE: 0%–70%

STEP: 5%

F11 LOW BATTERY ALARM ON SET POINT

Sets when the Low Battery Alarm goes ON point based on percent of

amp hours discharged. F11 is displayed as a percentage: i.e. 10 is 10%
discharged. F11 may set anywhere in its range but at least 10% below
the F10 Low Battery Alarm OFF Set Point set point.

DEFAULT: 80% RANGE: 10%–80%

STEP: 5%

F10

TURNS ON Low Battery

Alarm at a set % of rate-

compensated amp hours

discharged

F11

TURNS OFF Low

Battery Alarm when

amp hours are restored

Refer to F14 in the Owner's Manual

Functions F10, F11, and F12 define operation of the Visual Low Battery
Alarm as follows:

0% Discharged

Amp-Hour

Capacity of

Battery

E.G. 100 Ah

ALARM ON

Settable Range

70% Discharged

10% Discharged

80% Discharged

ALARM OFF
Settable Range