Types and versions – VEGA VEGASON 54V…56V User Manual

Page 12

Advertising
background image

12

VEGASON 54V … 56V

1 … 2 sensors on VEGAMET 515V signal conditioning instrument

• Two-wire technology, supply from the signal conditioning instrument, output signals and

voltage supply via one two-wire cable.

• Digital output signal, two sensors on one cable.
• Display of measured values in the sensor and in the signal conditioning instrument.
• Optional external indicating instrument (can be mounted up to 25 m separated from the

sensor in Ex area).

• Adjustment with the PC, the signal conditioning instrument or adjustment module MINICOM

(can be plugged into the sensor or the external indicating instrument VEGADIS 50).

• Max. resistance of the signal cable 15

W per wire or 1000 m cable length.

1)

Sensor cables should be screened. Grounding of
the cable screens at both ends is recommended.
However make sure that no earth compensation
currents flow via the screens
Earth compensation currents can be avoided by
potential equalisation lines or if the cable screen is
grounded at both ends - by connecting one end
(e.g. in the switching cabinet) via a capacitor (e.g.
0.1 µF; 250 V) to earth potential.

Types and versions

2

2

4

2

VEGAMET

515V

4

Current outputs
Voltage outputs
Relays
Digital wiring
Fault signals

Screened cable in case of electro-
magnetic interferences

1)

VEGACONNECT 2

VEGAMET 515 V signal conditioning
instrument in housing type 505
Processings see also product informa-
tion "Signal conditioning instruments
series 500"

VEGADIS 50

VEGADIS 50

RS 232

Advertising