4 technical data – VEGA VEGALOG 571 User Manual

Page 10

Advertising
background image

10

VEGALOG 571

Product description

1.4 Technical data

Common data (except VEGASTAB 593)

Power supply

Operating voltage of the cards

U

nom

= 24 V DC (18 … 36␣ V)

Power consumption
- CPU-card

max. 6 W

- EA-card

max. 11 W

- EV-card

max. 10 W

- AA-card

max. 9 W

- AD-card

max. 10 W

- AR-card

max. 6 W

- AT-card

max. 6 W

- VEGACOM 557

max. 6 W

Fuse

1 A slow-blow

Electrical connection

Module card

multiple plug acc. to DIN 41 612, series F,
48-pole (d, b, z) with coding hole

Module in carrier BGT LOG 571

suitable multipoint connector acc. to DIN 41 612
with connection via standard technologies

Electrical protective measures

Protection
not mounted

IP 00

in carrier BGT LOG 571
- front side completely equipped

IP 40

- upper and lower side

IP 20

- wiring side

IP 00

Protection class

I (in carrier BGT LOG 571)

Overvoltage category

II

CE-conformity

The module cards of VEGALOG 571 meet the protective regulations of EMVG
(89/336/EWG) and NSR (73/23/EWG). The conformity has been judged acc. to the following
standards:
EMVG Emission

EN 50 081 - 2

Susceptibility

EN 50 082 - 1

NSR

EN 61 010

Ambient conditions

Permissible ambient temperature

-20

°

C … +60

°

C

Storage and transport temperature

-20

°

C … +80

°

C

Mechanical data

Series

module cards for carrier
BGT LOG 571

Dimensions, not mounted

W = 25,4 mm (5 TE), H = 128,4 mm (3 HE),
D = 166 mm

Weight per card

approx. 400 g