VEGA VEGALOG 571 User Manual

Page 13

Advertising
background image

VEGALOG 571

13

AA-card

Current outputs

Number

10 outputs

Function

analogue output of processing results

Range

0/4 … 20 mA
(current limitation or fault signal 22 mA)

Load

max. 750

Resolution

0,05 % of range (10

µ

A)

Linearity error

0,025 % of range

Temperature error

0,025 %/10 k of range

Load dependent error

with load of 750

: 0,5 % (100

µ

A)

Interfaces

To LOGBUS

via LOGBUS-plug on the module cards

Electrical separating measures

Galvanic isolation
acc. to VDE 0106, part 1

between power supply, LOGBUS-connection

and current outputs

- reference voltage

250 V

Common potential

between current outputs (GND)

Indicating elements

LED in front facia

green (on): mains voltage on
red: fault signal

AD-card

DISBUS-output

Number

1 output

Function

digital transmission of processing results
and system information to VEGADIS 174

Number of instruments to be connected

max. 2 x 15 VEGADIS 174

Connection line

2-wire (screening recommended)

Max. line length

1000 m

Max. line resistance

15

per wire

Interfaces

To LOGBUS

via LOGBUS-plug on module card

Electrical separating measures

Galvanic isolation
acc. to VDE 0106, part 1

between power supply, LOGBUS-connection

and DISBUS-output

- reference voltage

250 V

Indicating elements

LED in front facia

green (on): operating voltage on
red: fault signal

Product description