2 mounting, 1 carrier, 2 mounting in carrier – VEGA VEGALOG 571 User Manual

Page 25

Advertising
background image

VEGALOG 571

25

2 Mounting

2.1 Carrier

The module cards of VEGALOG 571 must
only be mounted into the 19“-carrier BGT
LOG 571, because only this carrier is pro-
vided with a special bus board for data
transmission between the CPU and the indi-
vidual peripheral cards of VEGALOG.

A VEGALOG 571 can consist of max. two
completely equipped carriers which are
connected via a pluggable bus line (see
3 Electrical connection). As the extension of
the pluggable bus cable is not allowed, both
carriers must be mounted directly one above
the other.

Note:

In the following cases we recommend the
mounting of a ventilator to prevent a tempera-
ture increase in the VEGALOG:
- when more than one carrier are mounted

one above the other

- when more than 2,5␣ W/TE are consumed in

the carrier

- when there is no air circulation in the range

of the carrier

Mounting

2.2 Mounting in carrier

The carrier BGT LOG 571 is supplied com-
pletely assembled. For mounting of the indi-
vidual module cards you only have to place
the modules in the required positions. A mod-
ule consists of:
- a multipoint connector acc. to DIN 41 612,

series F, 48-pole (d, b, z)

- two screws
- two coded pins
- two guide rails.

The multipoint connector is available in the
following versions:
- Wire-Wrap standard connection

1,0 mm x 1,0 mm

- Plug connection 2,8 mm x 0,8 mm
- Termi-Point standard connection

1,6␣ mm␣ x␣ 0,8␣ mm

- Soldering connection
- Screw terminals 0,5 mm

2

Please note the operating instructions of the
carrier BGT LOG␣ 571, for mounting the mod-
ule.

19" = 482,6

465

84 TE = 426,72

57,1

132,5

10,5

7,5

258

3

185

Ventilator