2 coupling of the carriers, 3 interface cable pc - vegalog, Configuration with two racks – VEGA VEGALOG 571 User Manual

Page 29

Advertising
background image

VEGALOG 571

29

3.2 Coupling of the carriers

If the number of available modules of a car-
rier is not sufficient, the VEGALOG 571 can
be completed by a second rack.

The carriers are positioned one beneath the
other and connected via a supplied bus
cable. The bus cable is inserted into a plug
connection on the rear of the bus board.

For the configuration with two racks, two
switch positions must be checked and, if
necessary, adjusted according to the follow-
ing table:
- hook switch for termination resistor
- slide switch.

Configuration with one rack

Hook switch

closed

Slide switch

position M

Configuration with two racks

Rack 1

Hook switch

closed

Slide switch

position M

Rack 2

Hock switch

open

Slide switch

position S

Electrical connection

3.3 Interface cable PC - VEGALOG

You connect the PC (with the VVO adjustment
software) to the VEGALOG’s CPU-card using
the RS␣ 232-interface cable (interlink cable)
supplied.

M

S

M

S

DCD

1

RxD

2

TxD

3

DTR

4

GND

5

NC.

6

NC.

7

NC.

8

NC.

9

1

2

3

4

5

6

7

8

9

DCD

RxD

TxD

DTR

GND

NC.

NC.

NC.

NC.

Hook switch

Slide switch

Rack 1
(modules
1…16)

Bus cable

Rack 2
(modules
17…32)

VEGALOG (CPU-card)

PC

Interlink cable