VEGALOG 571
Product description
AR-card
Relay outputs
Number
10 outputs
Hysteresis
adjustable
Contact
1 floating spdt each
AgNi and hard gold plated
Turn-on voltage
min. 10 mV DC
max. 250 V AC, 60 V DC
Switching current
min. 10
µ
A DC
max. 2 A AC, 1 A DC
Breaking capacity
max. 125 VA, 54 W
Interfaces
To LOGBUS
via LOGBUS-plug on the module card
Electrical separating measures
Reliable separation acc. to VDE 0106,
from relays to the power supply and
part 1
LOGBUS-connection
- reference voltage
250 V
- isolation resistance
2,3 kV
Galvanic isolation between
among relays
- reference voltage
250 V
- isolation resistance
1,5 kV
Indicating elements
LED in front facia
green (on): operating voltage on
yellow/red: switching condition as level/
fail safe relay for each relay
red: fault signal
AT-card
Transistor outputs
Number
10 outputs
Turn-on voltage
max. 36 V DC
Switching current I
C
max. 60 mA, short circuit proof
Voltage loss U
CE
≤
1,5 V at I
B
= 60 mA
Interfaces
To LOGBUS
via LOGBUS-plug on the module card