VEGALOG 571

15

Electrical separating measures

Galvanic isolation
acc. to VDE 0106, part 1

between power supply, LOGBUS-connection

and transistor outputs

- reference voltage

250 V

Potential separation between

among transistor outputs

- reference voltage

50 V

- isolation resistance

0,5 kV

Indicating elements

LED in front facia

green (on): operating voltage on
yellow/red: switching condition as level/
fail safe transistor for each output
red: fault signal

VEGACOM 557

Meas. data input DISBUS
(only used in conjunction with VEGAMET signal conditioning instrument)

Data transmission

DISBUS (digital data transmission)

Connection line

2-wire, screening recommended

Line length

max. 1000 m

Meas. data input LOGBUS

Data transmission

LOGBUS (digital data transmission)

Connection line

connection via BUS-plug

PC-interface

Interface standard

RS 232 C

Line length

max. 15 m

Transmission rate

300, 600, 1200, 2400, 4800, 9600 and

19200 baud

Transmission format

8 data bits, 1 stop bit, even parity or

no parity

Plug in the front facia

D-SUB-plug connector, 9-pole, pins

Electrical separating measures

Reliable separation acc. to VDE 0106,

between power supply, LOGBUS, DISBUS,

part 1

PC-connection and appropriate interface

- reference voltage

250 V

- test voltage

3 kV

Indicating elements

LED in front facia

green BA: communication signal (bus activity)
red (flashing): DISBUS/LOGBUS-failure
red (permanently): failure
green on: operating voltage on

Interface data

see operating instruction VEGACOM 557

Product description

Advertising