VEGA VEGALOG 571 User Manual

Page 11

Advertising
background image

VEGALOG 571

11

CPU-card

Interfaces

To LOGBUS

via LOGBUS-socket on the module card

RS 232 via PC

via 9-pole D-SUB-socket (pins)

in the front plate of the module card

Electrical separating measures

Galvanic isolation
acc. to VDE 0106, part 1

between power supply, LOGBUS-connection

and RS 232-interface

- reference voltage

250 V

- isolation resistance

2,3 kV

Indicating elements

LED in front plate

green (on): operating voltage on
red: fault signal

EA-card

Meas. data inputs

Number

10 inputs

Kind

analogue two-wire input,
active or passive also mixed

Range

0 … 20 mA

Sensors

capacitive electrodes
hydrostatic pressure transmitters
vibrating level switches
conductive electrodes
process and differential pressure transmitters

Further connection possibilities

external current sources 0 … 20 mA, switching
contacts

Sensor supply voltage

24 V DC

Current limitation

per sensor circuit 26,5 mA, permanently short
circuit-proof

Max. input voltage

24 V DC

Switching threshold

adjustable via adjustment software VVO

in the range of 4 … 20 mA

Min. hysteresis

80

µ

A (fixed)

Linearity error

0,1 % of range (for input active and passive)

Average gradient failure

0,5 % of range (only for input passive)

Temperature failure

0,025 %/10 k of range

Connection line

2-wire (standard line)

Resistance per conductor

max. 35

Interfaces

To LOGBUS

via LOGBUS-plug on the module card

Product description

Advertising