4.4 Configuration and parameter

adjustment

No matter whether you set up your
VEGAMET via the keys of the adjustment
module or via a PC with the software VVO,
the procedure is always the same.

Proceed in the following sequence:
- configuration (if not already configured as

factory setting)

- parameter adjustment.

In this operating instructions manual the ad-
justment steps are described which are
carried out directly on the keys of VEGAMET.
The adjustment via the software VVO is de-
scribed in a separate manual.

Configuration

Configuring means coordinating and assign-
ing (one time) functions. VEGAMET requires
a (mostly once) basic co-ordination, a deter-
mination of applications and an assignment of
inputs and outputs. There is a choice of ex-
isting functions and possibilities. This proce-
dure is called configuration. The signal
conditioning instruments are delivered with a
configuration which only needs to be
changed in special cases.

The basic configuration includes the following
steps:

1 Configuration measurement loop

• Choose the kind of application (level,

gauge…)

• Choose sensor type (hydrostatic, ultra-

sonic…)

• Determine application (standard, level

difference…)

• Determine options (no option, correc-

tions…)

Note:

The measurement loop configuration can only
be modified if a "Reset to single measure-
ment“ has been carried out before (under
"Additional functions“ in the reduced menu). If
you only want to modify the sensor type, you
first have to carry out "Reset TAG 1“ (under
"Additional functions“ in the reduced menu).

2 Configuration inputs

• Determine from where your VEGAMET

receives the input data (sensor, other
VEGAMET)

• Enter sensor characteristics values (meas.

range, current range)

3 Configuration outputs

• All outputs (except fail safe relay) can been

assigned to one sensor or can be switched
off.

After basic configuration, VEGAMET goes
into operating condition and indicates the
actual measured value. The other configura-
tions should be carried out after the param-
eter adjustment.

Parameter adjustment

Parameter adjustment means changing the
values. Signal conditioning instruments have
many parameters, the values of which can be
modified, such as for example the integration
time of 0 … 600 s. The modification of these
values is called parameter adjustment. The
parameter adjustment does not influence the
configuration. Take notice that parameter
adjustment is only possible after a configura-
tion has been carried out (e.g. set values of
the current input when the current output has
been assigned).