6.8 Simulation

To check outputs and connected instruments,
you can adjust any individual percentage
value with the keys [+] and [–] in this menu
item. Initial point is always the actual meas-
ured value. The indicated value flashes when
simulation is activated. 15 minutes after set-
ting the simulated value, the simulation auto-
matically terminates and resets to meas.
value indication.

Settings in the "reduced menu“

TAG-
No. 1
%
xx,x

Param.
TAG-
No. 1

Ad-
just-
ment

Signal
condi-
tioning

Out-
puts

Simu-
lation
now!
OK ?