Level measurement with density correction, Settings in the "extended menu – VEGA VEGAMET 514V User Manual

Page 28

Advertising
background image

28

VEGAMET 514V

Settings in the "extended menu“

Level measurement with density correction

Level measurement with density
correction

TAG 1
Level

Appli-
cation

Level

Sensor
type

Hydro-
static

Mode

Stan-
dard

Option

Density
corr.

Sensor
coordi-
nation

Posi-
tion A

In-
put1

Posi-
tion E

In-
put4

Offset correction

- with unpressurized sensor
- parallel shift of the adjust-

ment characteristics

Real value correction

- with available percentage

value

- parallel shift of the adjust-

ment characteristics

Density correction

- only in conjunction with

hydrostatic pressure
transmitters

- steepness correction of

the adjustment character-
istics

Offset correction

0

100%

0

100%

corrected measured value e.g. 0 %

Measured value too low

incorrect course of measured values

Measured value too high

actual measured value
in %

Pos. D

Real value correction

Density correction

incorrect course of measured values

incorrect course of measured values

greater density,
measured value too high

lesser density,
measured value too low

0

100%

0

40

100%

40

0

20

100%

0 20

100%

Measured value too low

Measured value too high

actual measured value
in %

actual measured value
in %

corrected measured value e.g. 20 %

corrected measured value e.g. 40 %

Pos. E

Pos. D

Pos. E

Pos. A

Pos. A

Pos. A

Pos. A