6 integration time, Settings in the "reduced menu – VEGA VEGAMET 514V User Manual

Page 21

Advertising
background image

VEGAMET 514V

21

Settings in the "reduced menu“

6.6 Integration time

Percent
Pressure
Mass

prop.
to

Height

Unit

m

dm
cm
….

TAG -
No. 1

m

2,341

TAG-
No. 1
%
xx,x

Param.
TAG-
No. 1

Ad-
just-
ment

Signal
condi-
tioning

Scal-
ing

Integr
ation
time s

0

Meas.
value
indication

If the integration time is set to 0 s (factory
setting), each quick change of the product
surface (e.g. waves) will be immediately
detected and interpreted as level change. All
output values of VEGAMET will follow the
wave movements. To avoid this, the integra-
tion time can be increased (max. 600 s are
possible with VEGAMET). The higher the time
setting, the slower the measured value
display reacts.

100 %

0 %

h=1.5 m

h=4.5 m

Scaling example

You have a raised tank and you want the
level to be indicated in meters with three
places after the decimal point.

Adjust the figure 1500 (with keys [+],
[–] and [OK]) in this menu item. This
corresponds to the level at 0 % (if
you want to have a lower resolution of

the meas. value indication, you can also ad-
just 150 or 15).

Adjust the figure 4500 (with keys [+],
[–] and [OK]) in this menu item. This
corresponds to the level at 100 %.

Adjust the decimal point as shown
(with keys [+], [–] and [OK]).

Choose the term "Height“ in this
menu item (with keys [+], [–] and
[OK]).

If you have chosen "Height“ in the
previous menu item, you get a choice
of several units (mm, dm, cm, m,
yard…). Choose m (with the keys
[+], [–] and [OK]).

In the meas. value indication, the
scaled value is shown.

0%
corres-
ponds

1500

100%
corres-
ponds

4500

Deci-
mal
point

8,888

2.341 m

Advertising