VEGAMET 514V

Error code

Meaning

Diagnosis

E061

Span of the voltage output values too small. The values for the voltage output
are too close togehter or are identical. Please check the adjustment of the
voltage output.

E063

Wrong sensor characteristics values. Please check the sensor characteristics
values

E102

A reset of the configuration was carried out on this VEGAMET via the key-
board.

E110

Switching hysteresis too small. The switching points are too close together or
are identical.

E111

Relay switching points exchanged. The relay switching points are reversed
with respect to the selected relay mode.