8 conditioning – VEGA VEGAMET 514V User Manual

Page 35

Advertising
background image

VEGAMET 514V

35

Settings in the "extended menu“

7.8 Conditioning

The menu items "

Scaling

“ and "

Integration

time

“ correspond to the menu items in the

"reduced menu“ (see appropriate chapter).

The menu item "

Density…

“ is optionally dis-

played when under "Configuration measure-
ment loop“ the appropriate sensor type has
been selected. The density value must,
before adjustment with medium, be so ad-
justed that it corresponds to the value of the
medium (see also chapter "Adjustment“).

The conditioning of VEGAMET can be
adapted to different vessel forms. The follow-
ing linearisation curves are available:
- linear (factory setting)
- horiz. cylindrical tank
- spherical tank
- Lin-curve 1
- Lin-curve 2
- Lin-curve 3

Lin-curves 1 … 3 can be edited by your-
self (see appropriate chapter).

After a scaling or linearisation, the required
output must be coordinated to the scaled or
linearised value (menu item "prop. to..." and
"Unit...") in the menu range "Parameter adjust-
ment outputs".

Under

Meas. value limitation

you can ex-

clude negative values.

Failure mode Standard

means that with a sensor current of 3.6 mA or
21 mA the fail safe relay responds.

Failure mode >110%

also causes a fault signal when a meas. value
of more than 110 % or less than -10 % is
reached.

Param.
TAG-
No. 2

like TAG-No. 1

Param.
TAG-
No. 1

Adjust-
ment

Signal
condi-
tioning

TAG -
No. 1
%
xx,x

Scaling

Lin.
curve

linear

0%
corres-
ponds

0

100%
corres-
ponds

1000

Integr
ation
time s

0

Den-
sity in
Kg/dm

3

1,000

Meas.
value
limita-
tion

Deci-
mal
point

888,8

prop.
to

unde-
fined

Unit

– –

nega-
tive
values

yes

Failure
mode

Stan
dard

cylindrical tank
etc.

>110%