VEGA VEGASON 71 - 2 … 75 - 2 User Manual

Page 10

Advertising
background image

Technical Information

10

71 - 2 … 75 - 2

Installation example for liquid tanks

-

Select sensor type and installation in relation to
max. level to be measured.

-

Protect the inner side of the socket piece for
corrosion or use non-corrosive material.

-

In case of round tank ceilings, the sensor should
be installed on a socket piece not located in the
centre or on an opening (on half radius).

In closed vessels:

Tube or direct mounting. If socket
piece length > 100 mm or for
VEGASON 72 / 73 or > 150 mm for
VEGASON 74 / 75 are required
(max. level). Note the dimensions
in the following table.

in open vessels:

Mounting via

Mounting by means

access hatch:

of bracketry

Simple direct mounting

Max. socket piece length L at:

(dimensions in mm)

VEGASON

71 - 2

72 - 2

73 - 2

74 - 2

75 - 2

at socket

100

300

400

400

–––

–––

piece ø

150

300

500

400

300

300

200

–––

–––

500

400

400

250

–––

–––

600

500

500

300

–––

–––

–––

600

600

350

–––

–––

–––

700

700

Min. distance

300

500

800

800

1000

L

ø

45

°

Socket piece length

Advertising