Measurement, Relay output

71 - 2 … 75 - 2

31

Module for relay output 1 … 4

The pulse-echo measuring system can be equipped
with max. two relay modules.

Each module has two relay outputs.

Two-point level switch

Mode coordination / meaning

module

relay

coordi-

mode

switching command

output

nation

1 and 2

1

1

0 - 43

0 - 44 = 1

0 - 45 and 0 - 46

2

0 - 48

0 - 49 = 1

0 - 50 and 0 - 51

2

3

0 - 53

0 - 54 = 1

0 - 55 and 0 - 56

4

0 - 58

0 - 59 = 1

0 - 60 and 0 - 61

Coordination

(Module 1, relay output 1)

MODE 0 - 43

For each relay output the coordination can be
programmed separately and relates to:

-

measurement (channel 1, 2 and difference)

-

measuring unit

-

level / volume percentage

vessel geometry / measuring result

measuring unit

coordination

linearization

(channel definition)

0 - 43

0 - 18, 0 - 28

level percentage

channel 1

m

= 1

%

= 2

0 - 18 = 1

channel 2

m

= 3

%

= 4

0 - 28 = 1

difference

m

= 5

%

= 6

volume percentage

channel 1

%

= 2

0 - 18 = 2

or 4 … 6

channel 2

%

= 4

0 - 28 = 2

or 4 … 6

difference

%

= 6

Mode

(Module 1, relay output 1)

MODE 0 - 44

Mode 0 - 44 = 1
two-point level switch
switching command 2 via
switching command 1
correspond to function A
(overfill protection)

0

25

75

100

50

% m

distance acc.t o sensor type

mode combination

switching command 2,
mode 0-46

switching command 1,

mode 0-45

(off)

(on)