VEGA VEGASON 71 - 2 … 75 - 2 User Manual

Page 43

Advertising
background image

Sensor optimization

71 - 2 … 75 - 2

43

Information for sensor optimization 1

If optimization is required, always compare the local
conditions with the programmed parameters - if
necessary correct or adapt.

Basic test of

Mode-no.

Information

Selection / measures

Page

1 - 09

product type

liquids or solids

p. 45

1 - 10

vessel geometry

vessel top flat or dished

p. 45

1 - 10

solid

define particle size /

p. 46

1 - 11

angle of repose

1 - 19

rate of level change

define in cm / sec.

p. 50

False echo tests

Mode-no.

Mode description

Page

False echo BEFORE useful echo (output too high)

1 - 07

start of working range

define

p. 44

1 - 14

17

false echo

learn (activate)

p. 48

1 - 18

profile interpolation

activate

p. 49

False echo AFTER useful echo (output too low)

1 - 08

end of working range

define

p. 44

1 - 12

/

13

multiple false echo

reduce

p. 47

1 - 21

/

22

max. gain

limited

p. 51

Supplementary programmings

1 - 23

measuring window

switched on or off

p. 52

1 - 24

false echo

determine

p. 52

1 - 25

real distance

program

p. 53

1 - 27

basic adjustment

define

p. 53

Above information for sensor optimization, relate to
sensor 1, channel 1.

Sensor optimization for sensor 2, channel 2 as
described on page 43 … 45, however mode

2 - 01

2 - 27

.