VEGA VEGASON 71 - 2 … 75 - 2 User Manual

Page 44

Advertising
background image

Working range reduction

44

71 - 2 … 75 - 2

Working range

MODE 1 - 05 … 1 - 08

The working range can be limited in this mode by
programming of
-

start of working range and

-

end of working range in case of failure.

Echoes outside this limitation are ignored, e.g.
-

false echoes in the narrow range

-

multiple echoes by reflection in empty vessels
(see programming example)

Note:
In case of multiple reflections, a limited operating
range may not be sufficient. The end of working
range should be programmed min. 10 % > than the
max. vessel height.

min. distance (e.g. VEGASON 74 - 2)

max. vessel distance

end of working range

max. distance (e.g. VEGASON 74 - 2)

Programming example:

Indication of distance in m ........................................

• can be indicated in mode 1 - 05

Indication of gain in dB .............................................

• can be indicated in mode 1 - 06

Start of working range ...............................................

• mode 1 - 07 is here indicated as programming

example

End of working range ................................................

• select mode 1 - 08 in MODEFIELD
• program 14.00 m in PARAMETER FIELD
• then store with STO-button

0 m

Mode 07 / 08

12

14

0,8

20

false echo by
reflections