VEGA VEGASON 71 - 2 … 75 - 2 User Manual
Page 50
Advertising
Adaptation to filling and emptying speed
50
71 - 2 … 75 - 2
Rate of product level change
MODE 1 - 19
The rate of product level change is factory set by
VEGA within the adjustment range
-
0.01 … 11 cm / sec. with
-
4.00 cm / sec.
This adjustment should only be changed if this
seems useful in case the actual rate of product
level change exceeds the standard value.
Programming example
Change to 0,50 cm / sec. .........................................
• select mode 1 - 19 in MODEFIELD
• program 0.50 in PARAMETER FIELD
• then store with STO-button
Conversion schedule .............................................
cm / sec.
m / hours
Adjustment range ........
0,01
0,36
0,05
1,8
0,1
3,6
0,5
18,0
1,0
36,0
2,0
72,0
4,0
144,0
6,8
216,0
8,0
288,0
10,0
360,0
Advertising