VEGA VEGASON 71 - 2 … 75 - 2 User Manual

Page 33

Advertising
background image

Measurement, Relay output

71 - 2 … 75 - 2

33

Using the VEGASON-measuring system in pump
stations allows several pumps to be used indepen-
dent of the level. Due to the different switching
commands there could be unequal pump running
times (and wear).

With programming the mode "pump function" the
switch on period of the respective relay outputs is
monitored via the central electronics. An automatic
change-over (priority determination) ensures
equality of pump running periods. See the following
example with three pumps.

Priority determination by:
-

switching on the measuring system

-

all relay outputs concerned in the pump function
switched off, i.e. with all pumps

-

with time interval, the time interval is active if
within the time programmed in mode 63 all
pumps are not stopped.
In this case first all relay outputs are switched
off, the actual priority will be determined and the
pumps will be switched on again in new
sequence after 10 secs.

Factory preset of mode 0 - 63 with

9999

minutes

^ approx. 1 week to the max interval time.

Note:
Before changing this time, it should be checked
if the (10 secs.) switch off of all pumps will create
a problem.

P3 on

% m

100

80

60

40

20

0

P2 on

P1 on

P3 off

P2 off

P1 off

P1 on

P2 on

P3 on

P1 off

P2 off

P3 off

P3

P2

P1

2h

4h

6h

6h

4h

2h

h

distance acc. to sensor type

running periods

= 8 h

= 8 h
= 8 h

Two-point level switch with pump function switch

Advertising