Measurement, Relay output

71 - 2 … 75 - 2

35

By parameter adjustment it is possible to define for
each relay output the tendency determination mode
and to coordinate this relay output to a channel.

The information for tendency determination is
formed of the rate of level change per time unit
(cm / min) and can be taken for raising and lower-
ing tendency.

The adjustment is made in cm / min. and detects a
range of 000.1 … 999.9 cm / min.

Programming example for tendency determination, e.g. 50 cm / min.

Coordination as described on page 31

Mode for relay output 1

.....................................

• select mode 0 - 44 in MODEFIELD
• program figure 3 in PARAMETER FIELD
• then store with STO-button

Tendency determination for relay output 1................

• select mode 0 - 45 in MODEFIELD
• program e.g. 050.0 (cm / min.) in PARAMETER

FIELD

• then store with STO-button

After above programming the relay output reacts as
follows:

with raising rate of level change

50 cm / min.

> 50 cm / min.

Same procedure for relay output 2 … 4, however
with respective modes, see above.

Mode coordination / meaning

module

relay

coordi-

mode

tendency

output

nation

1

1

0 - 43

0 - 44 = 3 or 4

0 - 45

2

0 - 48

0 - 49 = 3 or 4

0 - 50

2

3

0 - 53

0 - 54 = 3 or 4

0 - 55

4

0 - 58

0 - 59 = 3 or 4

0 - 60

Tendency determination
relating to increasing level
example relay output 1

Requirement:
-

enquire mode 3 (parameter 3) in mode 0 - 44

-

program the value of the required tendency
determination in mode 0 - 45

Procedure:
-

relay is not operated

-

if the level raises quicker than programmed in
mode 0 - 45, the relay energizes

-

if the filling speed is the same or lower than the
given value, the relay de-energizes again

11

9

10

11

9

10

Tendency determination