VEGA VEGAPULS WL 61 4 … 20 mA_HART - two-wire User Manual

Page 18

Advertising
background image

18

4 Mounting

VEGAPULS WL 61 • 4 … 20 mA/HART - two-wire

38061-EN-121011

1

Fig. 14: Position of the polarisation level
1 Marking bar

When mounting the sensor, keep a distance of at least 200 mm

(7.874 in) to the vessel wall. If the sensor is installed in the center of

dished or round vessel tops, multiple echoes can arise. These can,

however, be suppressed by an appropriate adjustment (see chapter

"Setup").
If you cannot keep this distance you should carry out a false echo

storage before setup. This applies mainly if buildup on the vessel wall

is expected. In this case, we recommend repeating a false echo stor-

age later with existing buildup.

> 200 mm

(7.87")

Fig. 15: Mounting of the radar sensor on round vessel tops

In vessels with conical bottom it can be advantageous to mount the

sensor in the center of the vessel, as measurement is then possible

down to the lowest point of the vessel bottom.

Installation position

Advertising