6 set up with vegadis 62, 1 connection, 2 adjust the sensor – VEGA VEGAPULS WL 61 4 … 20 mA_HART - two-wire User Manual
Page 25
25
6 Set up with VEGADIS 62
VEGAPULS WL 61 • 4 … 20 mA/HART - two-wire
38061-EN-121011
6 Set up with VEGADIS 62
6.1 Connection
The VEGADIS 62 is an indicating and adjustment unit without external
energy for looping into 4 … 20 mA/HART circuits.
The parameter adjustment of the sensor is carried out via HART com-
munication. During the parameter adjustment, the VEGADIS 62 acts
as a Secondary Master with respect to the sensor.
~
=
1
2
4
3
Fig. 24: Connection of VEGADIS 62 to the sensor
1 Sensor
2 VEGADIS 62
3 HART resistance > 150 Ω (necessary with low impedance power supply)
4 Voltage supply/Processing
The following adjustment volume of the connected HART sensor is
available:
•
Min./Max. adjustment
•
zero/span adjustment (live adjustment)
•
Damping
6.2 Adjust the sensor
Proceed as follows for the min./max. adjustment of the sensor:
1. Press "OK" to reach the adjustment menu.
2. Select the submenu "Measurement" and confirm with "OK".
3. Move to the menu item "Unit". There the instrument unit of the
sensor is displayed, for example "m".
4. Move to the menu item "MB begin", there the max. measuring
distance is displayed, for example the default setting 15 m.