7 Setup with PACTware

VEGAPULS WL 61 • 4 … 20 mA/HART - two-wire

38061-EN-121011

If these values are not known, an adjustment with the distances of for

example 10 % and 90 % is possible. Starting point for these distance

specifications is always the seal surface of the thread or flange. By

means of these settings, the real level will be calculated.
The real product level during this adjustment is not important, be-

cause the min./max. adjustment is always carried out without chang-

ing the product level. These settings can be made ahead of time

without the instrument having to be installed.

All device DTMs are available as a free-of-charge standard version

and as a full version that must be purchased. In the standard version,

all functions for complete setup are already included. An assistant for

simple project configuration simplifies the adjustment considerably.

Saving/printing the project as well as import/export functions are also

part of the standard version.
In the full version there is also an extended print function for complete

project documentation as well as a save function for measured value

and echo curves. In addition, there is a tank calculation program as

well as a multiviewer for display and analysis of the saved measured

value and echo curves.
The standard version is available as a download under www.vega.

com/downloads and "Software". The full version is available on CD

from the agency serving you.

7.3 Saving the parameter adjustment data

We recommend documenting or saving the parameter adjustment

data via PACTware. That way the data are available for multiple use or

service purposes.