28

7 Setup with PACTware

VEGAPULS WL 61 • 4 … 20 mA/HART - two-wire

38061-EN-121011

7 Setup with PACTware

7.1 Connect the PC

1

2 4

3

5

OPEN

TWIST

USB

LOCK

Fig. 25: Connecting the PC to the signal cable
1 Sensor

2 HART resistance 250 Ω (optional depending on processing)

3 Connection cable with 2 mm pins and terminals

4 Processing system/PLC/Voltage supply

5 Interface adapter, for example VEGACONNECT 4

Note:

With power supply units with integrated HART resistance (internal

resistance approx. 250 Ω), an additional external resistance is not

necessary. This applies, e.g. to the VEGA instruments VEGATRENN

149A, VEGAMET 381, VEGAMET 391. Common Ex separators are

also usually equipped with a sufficient current limitation resistance. In

such cases, the interface converter can be connected parallel to the

4 … 20 mA cable (dashed line in the previous illustration).

Via interface adapter to

the signal cable

Advertising