Integrated clock
Date format

Day.Month.Year

Time format

12 h/24 h

Time zone Ex factory

CET

Measurement electronics temerature
Resolution

1 °C (1.8 °F)

Accuracy

±1 °C (1.8 °F)

Voltage supply
Operating voltage

Ʋ Non-Ex instrument

9.6 … 36 V DC

Ʋ Ex-ia instrument

9.6 … 30 V DC

Interpolation protection

Integrated

Permissible residual ripple - Non-Ex, Ex-ia instrument

Ʋ for 9.6 V< U

N

< 14 V

≤ 0.7 V

eff

(16 … 400 Hz)

Ʋ for 18 V< U

N

< 36 V

≤ 1.0 V

eff

(16 … 400 Hz)

Load

see diagram

1200

927

500

750

250

12

18

16

9,6

14

20

15,1

22

24

26

28

30

32

34

36

V

1

4

2

3

Fig. 46: Voltage diagram
1 HART load

2 Voltage limit Ex-ia instrument

3 Voltage limit non-Ex/Ex-d instrument

4 Operating voltage

Electrical protective measures
Protection rating

IP 66/IP 68 (2 bar)

Overvoltage category

III

Protection class

III

Approvals
Instruments with approvals can have different technical data depending on the version.
For that reason the associated approval documents of these instruments must be carefully noted.

They are part of the delivery or can be downloaded under www.vega.com and "VEGA Tools" as

well as under "Downloads" and "Approvals".