3 scale the indication – VEGA VEGAPULS WL 61 4 … 20 mA_HART - two-wire User Manual
Page 26
26
6 Set up with VEGADIS 62
VEGAPULS WL 61 • 4 … 20 mA/HART - two-wire
38061-EN-121011
5. Edit value via "OK" and adjust the requested value, for example,
5 m.
6. Save value with "OK", VEGAPULS WL 61 displays briefly "Wait",
then the value is taken over into the sensor.
7. Move to the menu item "MB end", there the min. measuring dis-
tance is displayed, for example the default setting 0 m.
8. Proceed accordingly for "MB end", enter for example the value
1 m and store.
The min./max. adjustment is finished.
After "[ESC]", the display shows the actually measured distance as
digital value in m and the level on the bargraph.
Keep in mind that the displayed values are anticyclical. With increas-
ing distance, the 4 … 20 mA value gets smaller and vice versa.
6.3 Scale the indication
Proceed as follows for indication of the level as digital value in %:
1. Press "OK" to reach the adjustment menu.
2. Select the submenu "Measurement" and confirm with "OK".
3. Select the menu item "Unit"
4. Select the unit "USER" and confirm with "OK".