9 Diagnosis, Asset Management and service

VEGAPULS WL 61 • 4 … 20 mA/HART - two-wire

38061-EN-121011

Fault description

Error pattern

Cause

Rectification

7. Measured value

jumps towards 0 %

during filling

Level

time

0

– Amplitude of a multiple echo

(vessel top - product surface) is

larger than the level echo

– Check parameter "Application",

especially vessel top, product

type, dished end, high dielectric

figure, adapt if necessary

– The level echo cannot be distin-

guished from the false echo at

a false echo position (jumps to

multiple echo)

– Remove/reduce false echo:

minimize interfering installa-

tions by changing the polariza-

tion direction

– Chose a more suitable installa-

tion position

8. Measured value

jumps towards 100 %

during filling

Level

time

0

– Due to strong turbulence and

foam generation during filling,

the amplitude of the product

echo sinks. Measured value

jumps to the false echo

– Carry out false signal suppres-

sion

9. Measured value

jumps sporadically to

100 % during filling

Level

time

0

– Varying condensation or con-

tamination on the antenna

– Carry out a false signal sup-

pression or increase false

signal suppression with con-

densation/contamination in the

close range by editing

10. Measured value

jumps to ≥ 100 % or

0 m distance

Leve

l

time

0

– Level echo is no longer

detected in the close range

due to foam generation or false

echoes in the close range. The

sensor goes into overfill protec-

tion mode. The max. level (0 m

distance) as well as the status

message "Overfill protection"

are outputted.

– Check measuring site: Antenna

must protrude out of the socket

– Remove contamination on the

antenna

– Use a sensor with a more suit-

able antenna

9.4 Measurement error during emptying

Fault description

Error pattern

Cause

Rectification

11. Measured value re-

mains unchanged in

the close range during

emptying

Level

time

0

– False signal larger than the

level echo

– Level echo too small

– Remove false echoes in the

close range. Check: Antenna

must protrude out of the socket

– Remove contamination on the

antenna

– Minimize interfering instal-

lations in the close range by

changing the polarization

direction

– After removing the false ech-

oes, the false signal suppres-

sion must be deleted. Carry out

a new false signal suppression

12. Measured value

jumps towards 0 %

during emptying

Level

time

0

– Echo from the tank bottom

larger than the product echo,

for example, with products with

ε

r

< 2.5 oil-based, solvents

– Check application parameters

Medium type, Vessel height and

Floor form, adapt if necessary