9 Diagnosis, Asset Management and service

VEGAPULS WL 61 • 4 … 20 mA/HART - two-wire

38061-EN-121011

Fault description

Error pattern

Cause

Rectification

13. Measured value

jumps sporadically to-

wards 100 % during

emptying

Level

time

0

– Varying condensation or con-

tamination on the antenna

– Carry out false signal suppres-

sion or increase false signal

suppression in the close range

by editing

– With bulk solids, use radar sen-

sor with purging air connection

Depending on the reason for the fault and the measures taken, the

steps described in chapter "Setup" must be carried out again or must

be checked for plausibility and completeness.

Should these measures not be successful, please call in urgent cases

the VEGA service hotline under the phone no. +49 1805 858550.
The hotline is also available outside the normal working hours on

seven days a week around the clock.
Since we offer this service worldwide, the support is in the English

language. The service itself is free of charge, the only costs involved

are the normal call charges.

9.5 Software update

The following components are required to update the sensor soft-

ware:

Sensor

Voltage supply

Interface adapter VEGACONNECT 4

PC with PACTware

Current sensor software as file

You can find the actual sensor software as well as detailed infor-

mation of the procedure under "www.vega.com/downloads" and

"Software".
Caution:

Instruments with approvals can be bound to certain software ver-

sions. Therefore make sure that the approval remains effective with a

software update.
You can find detailed information on www.vega.com/downloads and

"Approvals".

9.6 How to proceed in case of repair

You can find a repair form as well as detailed information on how to

proceed under www.vega.com/downloads and "Forms and certifi-

cates".
By doing this you help us carry out the repair quickly and without hav-

ing to call back for needed information.
If a repair is necessary, please proceed as follows:

Print and fill out one form per instrument

Clean the instrument and pack it damage-proof

Reaction after fault recti-

fication

24 hour service hotline