PowerWalker VFI 10000TCP 3_1 User Manual

Page 15

Advertising
background image

12

3) Operating Environment

Temperature

Humidity

Altitude

Storage temperature

0

°

C-45

°

C

<95%

<1000m

-15

°

C-50

°

C

Note: if the UPS is installed or used in a place where the altitude is
above than 1000m, the output power must be derated in use, please
refer to the following:

Altitude (M) 1000 1500 2000 2500 3000 3500 4000 4500 5000

Maximum

Power

100% 95% 91% 86% 82% 78% 74% 70% 67%

Output

Voltage

Regulation

Power
Factor

Frequency

tolerance.

Distortion

Overload capacity

Current

crest ratio

±

1%

0.9 lag

Synchronized
50/60Hz

±

10%

in Line mode
(AC mode)

±

0.1% of

normal
frequency in
Battery mode

THD<2%

Full load

(Linear

Load)/

<5% for

reference

non-linear

load

100%-110% load
transfers to Bypass
mode after 5
minutes

110%-130% load
transfers to Bypass
mode after 1
minutes

130%-150% load
transfers to Bypass
mode after 10
second

>150% load
transfers to Bypass
mode after 2 second

3:1