PowerWalker VFI 10000TCP 3/1 model

Fig. 4-6 Input and output Terminal Block wiring diagram

Important notes: If the UPS is used in single mode, JP1 and JP2 must
be connected. If the UPS is used in parallel mode, the Jumper between
JP1 and JP2 must be removed.

Use cable cross section and protective device specification

Model

PowerWalker VFI

10000TP 3/1

PowerWalker VFI

20000TP 3/1

Input L1,L2,L3

Min.conductor cross section[mm

2

]

Max.conductor cross section[mm

2

]

2.5

4

6

10

Input L1,L2,L3 breaker (A)

40A,250VAC

60A,250VAC

Input N, M2

Min.conductor cross section[mm

2

]

Max.conductor cross section[mm

2

]

10

13

21

25

Input M2 breaker (A)

63A,250VAC

100A,250VAC

Input fuse (A)

30A,250VAC

50A,690AC

Output L,N,

Min.conductor cross section[mm

2

]

Max.conductor cross section[mm

2

]

10

13

21

25