3 trouble shooting in else cases – PowerWalker VFI 10000TCP 3_1 User Manual

Page 57

Advertising
background image

54

Inv Under Voltage

Alarm code:33

UPS internal fault Consult dealer.

Inv Softstart Fail

Alarm code:34

UPS internal fault Consult dealer.

Negative Power Fault

Alarm code:E1

The load is pure
inductive and
capacitive

Remove some non-critical loads.

Bypass supplies the load first, ensure
there is no overload, then turn on UPS.

Cable male and female
Loss fault

Alarm code:E2

The parallel cable
is disconnected

Check the parallel cable.

Backfeeder

Alarm code:93

UPS internal fault

Don’t touch any terminal of the
equipments which connect one utility
power with the UPS even you cut off the
utility power. Please Consult dealer.

7.3 Trouble Shooting In Else Cases

Problem

Possible cause

Remedy

No indication, no

warning tone even

though system is

connected to mains

power supply

No input voltage

Check the building wiring and input

cable.

Check if the input breaker is closed.

BYPASS LED light up

even though the power

supply is available

Inverter not switched

on

Press On-Switch “I” to turn on UPS.

BATTERY LED lights up,

and audible alarm

sounding every 1 beep

in every 4 seconds

Input voltage and/or

frequency are out of

tolerance

Check input power source.

Check the building wiring and input

cable.

Check if the input breaker is closed.