PowerWalker VFI 10000TCP 3_1 User Manual

Page 55

Advertising
background image

52

Heatsink Over
Temperature

Alarm code:86

Inside temperature of
UPS is too high

Check the ventilation of UPS and
the ambient temperature.

Para Cable Male Loss

Alarm code:E3

The parallel cable is
disconnected

Check the parallel cable.

Para Cable Female Loss

Alarm code:E4

The parallel cable is
disconnected

Check the parallel cable.

Para Bat Differ

Alarm code:E6

The battery packs of
some UPSs are
disconnected

Check if all the battery pack is
connected.

Para Byp Differ

Alarm code:E8

(PowerWalker VFI
10000TCP 3/1 mode
has no this case)

The M2 bypass input of
some UPSs is
disconnected

Check the building wiring and
input cable.
Check if the M2 breaker is closed.
Ensure the UPSs are connected to
same input source.

Para Line Differ

Alarm code:E7

The M1 line input of
some UPSs is
disconnected

Check the building wiring and
input cable.
Check if the M1 breaker is closed.
Ensure the UPSs are connected to
same input source.

Para Work Mode Differ

Alarm code:E9

There are different
power strategy setting
in parallel system

The UPSs with different power
strategy setting (Ex. one Line
mode and one Converter mode)
are forbidden to parallel.

Para Rate Power Differ

Alarm code:EA

There are different UPSs
in parallel system

The UPSs with different capacity
(Ex. one 10KVA and one 20KVA)
are forbidden to parallel.

ECO In Para

Alarm code:EB

HE function is enabled
in parallel system

HE function is forbidden in parallel
system.