2 trouble shooting according to fault indication – PowerWalker VFI 10000TCP 3_1 User Manual

Page 56

Advertising
background image

53

7.2 Trouble Shooting According To Fault Indication

Problem Displayed

Possible cause

Remedy

Inv Overload Fault

Alarm code:42

Overload

Check the loads and remove some

non-critical loads.

Check if some loads are failed.

Byp Overload Fault

Alarm code:43

Overload

Check the loads and remove some

non-critical loads.

Check if some loads are failed.

Output Short Circuit

Alarm code:31

Output short
circuit

Remove all the loads. Turn off the UPS.

Check if UPS output and loads is short

circuit.

Ensure short circuit is removed before

turning on again.

Heatsink Over
Temperature Fault

Alarm code:81

Inside
temperature of
UPS is too high

Make sure the UPS is not overloaded; the

air vents are not blocked and the

ambient temperature is not too high.

Wait for 10 minutes for the UPS to cool

down before turning on again. If failed,

please contact the distributor or service

center.

Bus Over Voltage

Alarm code:21

UPS internal fault Consult dealer.

Bus Under Voltage

Alarm code:22

UPS internal fault Consult dealer.

Bus Unbalance

Alarm code:23

UPS internal fault Consult dealer.

Bus short

Alarm code:24

UPS internal fault Consult dealer.

Bus Softstart Fail

Alarm code:25

UPS internal fault Consult dealer.

Inv Over Voltage

Alarm code:32

UPS internal fault Consult dealer.

Advertising