6.5 Backfeed Protection

To support protection against UPS backfeeding a new logic is integrated

into PowerWalker VFI 10000-20000TP 3/1 model. But in PowerWalker

VFI 10000TCP 3/1 model

there’s no this function.

Using backfeed protection

On customers side an additional external isolation device (magnetic

contactor, MC or minimum voltage tripping device) must be provided as

shown in Fig. 6-3. The isolation device must be able to carry the UPS

input current (see resp. table of basic UPS operating instructions).

The isolation device has to be installed in the bypass source path.

Cabling of the backfeed terminals contains a jumper and two cables to

the optional external isolation device.