For safety, please cut off the mains power switch before installation.

1) Open the terminal block cover located on the rear panel of the

UPS, please refer to the appearance diagram.

2) For tower PowerWalker VFI 10000TCP 3/1 UPS, it is

recommended to select the UL1015 8AWG(10mm

2

) wire or other

insulated wire which complies with AWG Standard for the UPS
input and output wirings.

3) For PowerWalker VFI 20000TP 3/1 UPS, it is recommended to

select the UL1015 6AWG(25mm

2

) wire or other insulated wire

which complies with AWG Standard for the UPS input and output
wirings.

Note: Do not use the wall receptacle as the input power source

for the UPS, as its rated current is less than the UPS’s
maximum input current. Otherwise the receptacle may be
burned and destroyed.

4) Connect the input and output wires to the corresponding input

and output terminals according to the following diagram.

Note: you must make sure that the input and output wires and

the input and output terminals are connected tightly.

5) The protective earth ground wire refers to the wire connection

between the equipment which consumes electric equipment and
the ground wire. The wire diameter of protective earth ground
wire should be at least as above mentioned for each model and
green wire or green wire with yellow ribbon wire is used.

6) After having completed the installation, make sure the wiring is

correct.

7) Please install the output breaker between the output terminal

and the load, and the breaker should with leakage current
protective function if necessary.