20

External Battery Cabinet Positive

Pole(+),Neutral pole,Negative

pole(-),

Min.conductor cross section[mm

2

]

Max.conductor cross section[mm

2

]

10

13

21

25

Line input Backfeed protection

device

A 4-pole disconnection device with

100A/250VAC, less than 15s break

time and min. 1.4mm clearance will be

used in final installation for backfeed

protection in line input.

M2 input Backfeed protection device A 2-pole disconnection device with

100A/250VAC, less than 15s break

time and min. 1.4mm clearance will be

used in final installation for backfeed

protection in line input.

Protective Earthing conductor[mm

2

]

Max.13

Max.25

Torque for fixing above terminals

(10 1b in)

(18 1b in)

Sheet.1 PowerWalker VFI 10000-20000TP 3/1 models

Model

PowerWalker VFI 10000TCP 3/1

Input L2,L3

Min.conductor cross section[mm

2

]

Max.conductor cross section[mm

2

]

2.5

4

Input L1,L2,L3,N switch (A)

63A,250VAC

Output switch(A)/maintain switch(A)

63A,250VAC

Input L1,N

Min.conductor cross section[mm

2

]

Max.conductor cross section[mm

2

]

10

13

Input fuse (A)

30A,250VAC

Output L,N,