8) To connect the load with the UPS, please turn off all the loads

first, then perform the connection and finally turn on the loads
one by one.

9) No matter the UPS is connected to the utility power or not, the

output of the UPS may have electricity. The parts inside the unit
may still have hazardous voltage after turning off the UPS. To
make the UPS have no output, power off the UPS, and then
disconnect the utility power supply.

10) Suggest charging the batteries for 8 hours before use. After

connection, turn the M1/M2/N input breaker (for PowerWalker
VFI 10000-20000TP 3/1), turn the input switch (for PowerWalker
VFI 10000TCP 3/1) in the "ON" position, the UPS will charge the
batteries automatically. You can also use the UPS immediately
without charging the batteries first, but the backup time may be
less than the standard value.

11) If it is necessary to connect the inductance load such as a

monitor or a laser printer to the UPS, the start-up power should
be used for calculating the capacity of the UPS, as its start-up
power consumption is too big when it is started.