PowerWalker VFI 10000TCP 3_1 User Manual

Page 50

Advertising
background image

47

6.4

PowerWalker VFI 10000TP 3/1

Optional Design of

Charger Current

6.4.1 Our charger output current has two optional levels

(2A&4A) for different battery pile.

6.4.2 Operate method:

2A charger current method

Insert short circuit pin 104-10000-01 in the CN7 position of charger
board. This is charging for 7AH*24 pcs or 9AH*24 pcs.

4A charger current method

Pull out short circuit pin 104-10000-01 from CN7 position of charger
board. This is for 2 piles of 7AH*24 pcs or 2 piles of 9AH*24 pcs.

Short circuit pin 104-10000-01