Establishing communication to Remote HMIs

30

6

6.1.2 Connect to the local network

Step 1: Connect the Entellisys system to the company network via the VPN/Firewall appliance in
the switchgear

Step 2: Verify communication between local HMI(s) and CPUs (See

Verify local communication to

CPU on page 32

)

Step 3: Install Remote HMIs (See

Remote HMI Software on page 35

Step 4: Verify communication between Remote HMI and CPUs

6.2 Changing the CPU IP address

To change the CPU IP addresses
1.
Navigate to the Communication tab from the Main Menu, User Settings, HMI Preferences
2.
Select either CPU A or CPU B by clicking the appropriate button.
3. Enter the new IP address. The IP address format is X.X.X.X where X is from 0 to 255.

Figure 6-1 CPU IP Address configuration screen on a Local HMI

NOTE: CPU IP address fields are read-only in the Remote HMI software. To configure Remote
HMIs, see

Configuring Lineups on page 38

.