Preparing and configuring a replacement CPU

58

12

12.2 Part II – Replacing the CPU

This wizard assists in replacing the CPU and modifying the IP Address Configuration, Firmware,
Option String, Settings, and CPU Commission options.

Step 0

Ensure that there is a valid option string on a USB, the replacement hardware is ready, the
serial numbers and IP addresses of both CPUs are known.

Disconnect Entellisys switchgear from all external networks at the HMI switch.

Navigate to the Replace CPU tab in the Maintenance dialog box, click Perform
Replacement
to begin the CPU replacement wizard.

Run steps 1-9 on the Local HMI.

NOTE: If Entellisys has not been disconnected from any external ethernet networks, the
replacement process may fail.

WARNING! If steps are skipped but have not been completed by re-starting the wizard, the
replacement CPU may not operate properly.

Step 1

The Step 1 – Select CPU dialog box displays again to confirm which CPU is to be replaced:

Figure 12-6 Step 1 – Select CPU dialog box