Pre-programming settings prior to

switchgear arrival

Entellisys provides a method for users to work on the system settings before the switchgear
arrives. Once the gear is installed and control power is applied, the saved settings can be written
to the system.

To pre-program Settings, the “Entellisys Remote HMI – User Interactive version” must be
purchased. GE will ship the Remote HMI software, System Administrator Manual (this manual),
and a System Archive when the switchgear ships from the factory.

The following steps should be performed to begin pre-programming:

Step 1: Install the “Entellisys Remote HMI – User Interactive version” software.
See

Remote HMI Software on page 35

for instructions.

Step 2: Install the System Archive provided by GE.
See

Restoring an archive on page 48

for instructions.

Step 3: Change to Offline Mode.
See

Offline mode on page 41

for instructions and for offline mode capabilities.

Step 4: Set User Settings.
See DEH-431 Entellisys Low Voltage Switchgear System User Manual.

Step 5: Install and Commission the Switchgear.
See

Commissioning the switchgear on page 11

for instructions.

Step 6: Configure the System for Remote Communications.
See

Establishing communication to Remote HMIs on page 29

for instructions.

Step 7: Write saved Settings to System.
See

Writing settings to a live system on page 43

for instructions.