Settings files and offline system configuration, 1 offline mode, 8settings files and offline system configuration – GE Industrial Solutions Entellisys 4.0 System Administrator Manual User Manual

Page 41

Advertising
background image

Offline mode

41

8

8

Settings files and offline system

configuration

All system settings are recorded locally in “Settings” files. These files are updated each time a
setting is modified and automatically updated every 30 minutes.

NOTE: Both CPUs must have the same configuration and settings at all times, otherwise
unpredictable system behavior could occur. Every 30 minutes the system compares the settings
between the CPUs. If a mismatch in settings between CPUs does occur, an event will be
generated. A mismatch should be correctly immediately.

8.1 Offline mode

The HMI has a special offline mode. Offline mode disconnects the HMI from a live system and
allows users to modify and save settings. Later, once reconnected to a live system, these saved
settings can be written to the system.

The following operations are permitted in offline mode:

User Settings activities

Maintenance activities

User Administration

Another convenience offline mode provides is the ability to work on protection settings prior to
the arrival of the switchgear. See

Commissioning the switchgear on page 11

for more details.