Part II – Replacing the CPU

63

12

Step 7

The option string will be written to the CPUs, after which they will automatically reboot. After
the reboot is complete, the dialog box for Step 7 will be displayed to update the settings of
the new unit. The option to skip the task is available if this has already been done.

HMI will now copy both factory configuration and user settings to the new CPU.

Figure 12-14 Step 7 – Copy Setting dialog box

Step 8

Click Next to commission the new CPU and activate all of the relaying and protection
algorithms in the unit.

Figure 12-15 Step 8 – Set CPU Commission dialog box